Practical experiences as an electrical engineer from rural electrification

September 6, 2017 | Autor: Samundra Gurung | Categoría: Electrical Engineering, Power System, Rural Electrification, Electric Power Systems
Share Embed


Descripción

Rural Electrification

Overview of topics • Survey of OHL • Design of Transmission and distribution system • Cost Estimate • Construction • Some pictures

Softwares you need • • • • •

Autocad MHP(Microhydro) design aids MS Excel Optional: ETAP, Power world simulator, Netbas

T/D process

Survey

Design

Construction

Transmission and Distribution(T& D) •

Types



Suspended Overhead on Poles (Overhead Line)



Buried Cables (Underground Cable) OH Line(Features)



Less Expensive



Frequent Maintenance Required



Less cost per maintenance



Does not look aesthetically good in dense locality



Not preferred in areas which experience heavy snowfall

• UG Cable

• Costly Installation(if done per standard 6 times costly compared to OH) • Less Maintenance • Higher cost per maintenance • Highly desirable in densely located areas • Obvious choice for areas which experience heavy snowfall

• ACSR (Aluminium Conductor Steel Reinforced) conductors are the norms of the day(as against hard drawn copper which were used in earlier days)

Components used • • • •

Transformers Poles Insulators Lightning arrestors and Earthing plates

Transformer • ONAN type • Step up transformer near to generating station of high KVA rating and stepdown of smaller KVA ratings near to load centers • Sizing is done taking load demand and dividing by suitable power factor

Data sheet

Conductor • • •

ASCR type Mainly Dog, Rabbit, Weasel, and Squirrel If dog is on phase, rabbit is taken in neutral ;similarly if rabbit is in phase weasel in neutral and so on

Comparison between conductors

Poles

Voltage level

230V

400V

11, 33kV

Insulator types

Shackle Insulators --Supported(Clamped)by D-Iron set which is a clamp made out of galvanized steel

Shackle Insulators of suitable voltage ratings upto 1000V OH Line

Shackle

S. No

Size

Dimensions

Weight

Corresponding conductor

1

Small

55 mm x 55 mm

200 gm

Squirrel, service wire

2

Medium

75 mm x 90 mm

600 gm

Gopher, weasel and rabbit

3

Large

100 mm x 110 mm

1300 gm

Dog

Disc insulator • Disc Insulators along with suitable tension Set are used for deadening a line at 11kV or higher.

Pin Insulator • Pin Insulators are used for straight runs of 11kV Line

Stay sets • Stay sets to support poles

• Suitable Stay sets are provided at first pole, at line end, at all poles set at an angle and at every fifth pole even if the poles are in a straight line • Two types 16mm dia for LT and 20mm dia for HT

Lightning arrestor and Earthing • Lightning Arrestors to protect lines from Lightning • 0.5kV ,ZnO (Gapless)Arrestors for 400Volt Line • 12kV, 5kA ZnO(Gapless) Arrestors for 11kV Line • Placed every 500m and on junctions and last(end) points • Drop Out(DO) Fuse to Protect Transformers from Over Current

Earthing system • 600mm*600mm*3.15 mm copper plate is used for earthing purposes(weighs around 10kg) • Plate is connected with 8SWG copper wire(4.06dia) • Earth Resistance value